Liquid Level Control
Model 31x
Dual Probe Conductance Sensing
Pump-up/Pump Down
Features
- 24 VAC operation 50/60 Hz
- Low voltage AC detection
- Selectable sensitivity to 100k ohms
- Probe currents less than 1 mA.
- 10A relay @ 240 VAC resistive
- 10,000,000 mechanical operations
- 100,000 full load operations
- Operating temperature to 85° C
- Conformal coat, moisture protection
- UL File E250761 US&C UL
Model type 31111 shown
The 31x series are conduction/resistance sensing
type liquid level controllers. Pump-up operation begins when
power is applied. With an empty tank, the control relay is
energized until liquid contacts the high probe. As the tank
is emptied and the liquid goes below the low probe the relay
again is energized and the cycle is repeated. Pump-down operation
is similar, with the control relay being energized upon liquid
contacting the high probe. The relay is de-energized upon
liquid contacting the high probe. The relay is de-energized
when liquid falls below the low probe.
Selection options
24 VAC operation
Sensitivity 50k or 100k ohms
Pump-up or pump-down mode
1/4 inch fast-on© or screw terminal connections
Contact Capable for additional options
Model 31x Product Characteristics
Power input: 24 VAC 50/60 Hz
Power consumption: 1.5 VA max.
Sensing range: 100k ohms max.
Sensing voltage: 20 VAC max.
Sensing current:1mA max.
Operating frequency: 50/60 Hz
Operating temperature: 85° C max
Operating humidity: 90% non-condensing
Output: 10A @ 240 VAC, 1/2 hp
Mechanical: 10,000,000 cycles
Electrical: 100,000 cycles min.
Connections: 1/4 male fast-on®
Terminal block optional
LED operation monitor
|
|
Liquid Level Control
Model 32x
Dual Probe Conductance Sensing
Pump-up/Pump Down
Features
- 120 or 240 VAC operation 50/60 Hz
- Low voltage AC detection
- Selectable sensitivity to 100k ohms
- Probe currents less than 1 mA.
- 10A relay @ 240 VAC resistive
- 10,000,000 mechanical operations
- 100,000 full load operations
- Operating temperature to 85° C
- Conformal coat, moisture protection
- UL File E250761 US&C UL
The 32x series are conduction/resistance sensing
type liquid level controllers. Pump-up operation begins when
power is applied. With an empty tank, the control relay is
energized until liquid contacts the high probe. As the tank
is emptied and the liquid goes below the low probe the relay
again is energized and the cycle is repeated. Pump-down operation
is similar, with the control relay being energized upon liquid
contacting the high probe. The relay is de-energized upon
liquid contacting the high probe. The relay is de-energized
when liquid falls below the low probe.
Selection options
120 or 240 VAC operation
Sensitivity 50k or 100k ohms
Pump-up or pump-down mode
1/4 inch fast-on© or screw terminal connections
Contact Capable for additional options
Model 32x Product Characteristics
Power input: 120/240 VAC 50/60 Hz
Power consumption: 1.5 VA max.
Sensing range: 100k ohms max.
Sensing voltage: 20 VAC max.
Sensing current:1mA max.
Operating frequency: 50/60 Hz
Operating temperature: 85° C max
Operating humidity: 90% non-condensing
Output: 10A @ 240 VAC, 1/2 hp
Mechanical: 10,000,000 cycles
Electrical: 100,000 cycles min.
Connections: 1/4 male fast-on®
Terminal block optional
LED operation monitor
|